The ENET-S7300-S function
1, support multi-master station communication, the expansion port can be connected to the touch screen or other main station.
2. Set the parameters and run to diagnose the device through the WEB server or the configuration diagnostic tool BCDevice.
3, Porter rate 9.6 Kbps ~ 6 Mbps adaptive.
4. Installed on the 35mm guide rail and connected to the PPI / MPI / PROFIBUS communication port of PLC via DP cable, requiring external 24VDC power supply.
5. Integrate WiFi function, support AP mode, STA mode and AP + STA mode.
6, PLC programming, data acquisition and data exchange through WiFi.
7. Support communication with Ethernet interfaces of S7-200, S7-200SMART, S7-1200 / 1500, S7-300 and S7-400 and ModbusTCP main slave station function.
8. The expanded nine-pin master port supports the main and slave station function of modbusRTU.
9. Support Siemens S7 Ethernet communication driver, including MicroWIN, STEP 7, Botu and WinCC, etc.
10. Users can adopt high-level language programming (such as VB, VC, C #, etc.) according to ENETS7 protocol to realize data communication with S7-200 / 300 / 400 and facilitate the development of production management system.
11. Provide the ENETS7 OPC server for free, and the SCADA supporting OPC channel to communicate with PLC in OPC mode.
12. Integrated ModbusTCP server, the Modbus data area can be automatically or edited to the S7-200 / 300 / 400 register.
13. It can realize S 7 TCP connection and ModbusTCP communication at the same time, and support up to 32 upper computer connections.
14, support the user side through Ethernet to achieve firmware update, one purchase, permanent upgrade.
Typical application
Typical application of ENET-S7300-S bridging type
technical parameter
product model |
ENET-S7300-S |
description |
The Siemens S7-300 Ethernet communication processor |
pigment |
Metal black |
situation display |
Pwr,Bus,WiFi |
Ethernet interface interface type output speed Protocol support linker number |
Link / Active indicator light, automatic polarity crossing RJ 45 female socket 10/100Mbps Siemens S 7 TCP, ModbusTCP, and ENETS7 The maximum is 32 |
WiFi joggle interface type transmitting power receiving sensitivity Wireless type Security mechanism Protocol support TCP linker number |
802.11 b/g/n 2.4G-2.5G External, high-gain antenna +26dBm(MAX,2.4G 802.11b/g/n) -89dBm(802.11b)、-74dBm(802.11g)、-72dBm(802.11n) Station/AP pattern WPA-PSK/WPA2-PSK/WEP Siemens S 7 TCP, ModbusTCP, and ENETS7 The maximum is 32 |
S7 interface interface type transmission speed Protocol support |
RS485 DSUB nine needle 9.6K,19.2K,187.5K,500K,1.5M, 3M, 6M, and Porter rate adaptation PPI / MPI slave station / MPI main slave station / PROFIBUS |
man-machine interface interface type output speed Protocol support Man-machine type |
RS485 The DSUB nine-pin mother 9.6K,19.2K,187.5K,500K,1.5M, 3M, 6M, and Porter rate adaptation MPI multi-master station protocol, ModbusRTU main and slave station Siemens, MCGS, Willen, Delta, Buke, etc |
programming software configuration software OPC software |
MircroWIN, STEP 7, Botu WinCC, Kunlun Pass, configuration king, Power Control, Jay Control, IFIX, INTOUCH, etc KepwareOPC、ENETS7 OPC |
Diagnostic and parameter settings tool |
IE browser, default 192.168.1.188, BCDevice |
power supply mode Voltage type |
PLC port power / external 24V 24VDC/100mA |
working temperature |
0~60℃ |
Working humidity |
95% Non-coagulation |
electromagnetic compatibility |
2014/30/EU |
attestation |
CE attestation |
Dimensions (L * W * H) |
115*27*75mm |
weight |
150g |