The ENET-S7200-S function
1, support multi-master station communication, the expansion port can be connected to the touch screen or other main station.
2. Set the parameters and run to diagnose the device through the WEB server or the configuration diagnostic tool BCDevice.
3, the baud rate 9.6Kbps~187.5Kbps is adaptive.
4. Install it on the 35mm guide rail, connect it to the PPI communication port of the PLC or the EM277 through the DP cable, and require external 24VDC power supply.
5. Integrate WiFi function, support AP mode, STA mode and AP + STA mode.
6, PLC programming, data acquisition and data exchange through WiFi.
7. Support communication with Ethernet interfaces of S7-200, S7-200SMART, S7-1200 / 1500, S7-300 and S7-400 and ModbusTCP main slave station function.
8. Support Siemens S7 Ethernet communication driver, including MicroWIN, and support WinCC to directly connect to S7-200 in TCP / IP mode.
9. Users can adopt high-level language programming (such as VB, VC, C #, etc.) according to the ENETS7 protocol to realize data communication with S7-200 and facilitate the development of production management system.
10. Provide ENETS7 OPC server for free. SCADA supporting OPC channel to communicate with PLC in OPC mode.
11. Integrated ModbusTCP server, Modbus data area can be automatically or edited to S7-200 register.
12. It can realize S 7 TCP connection and ModbusTCP communication at the same time, and support up to 32 upper computer connections.
13, support user side through Ethernet firmware update, one purchase, permanent upgrade.
Typical application
technical parameter
product model |
ENET-S7200-S |
description |
The Siemens S7-200 Ethernet communication processor |
pigment |
Metal black |
situation display |
Pwr,Bus,WiFi |
Ethernet interface interface type output speed Protocol support linker number |
Link / Active indicator light, automatic polarity crossing RJ 45 female socket 10/100Mbps Siemens S 7 TCP, ModbusTCP, and ENETS7 The maximum is 32 |
WiFi joggle interface type transmitting power receiving sensitivity Wireless type Security mechanism Protocol support TCP linker number |
802.11 b/g/n 2.4G-2.5G External, high-gain antenna +26dBm(MAX,2.4G 802.11b/g/n) -89dBm(802.11b)、-74dBm(802.11g)、-72dBm(802.11n) Station/AP pattern WPA-PSK/WPA2-PSK/WEP Siemens S 7 TCP, ModbusTCP, and ENETS7 The maximum is 32 |
S7 interface interface type transmission speed Protocol support |
RS485 DSUB nine needle 9.6K,19.2K,187.5K, Porter rate autoadaptation The PPI / MPI slave station |
man-machine interface interface type output speed Protocol support Man-machine type |
RS485 The DSUB nine-pin mother 9.6K,19.2K,187.5K, Porter rate autoadaptation The PPI / MPI slave station Siemens, MCGS, Willen, Delta, Buke, etc |
programming software configuration software OPC software |
MircroWIN WinCC, Kunlun Pass, configuration king, Power Control, Jay Control, IFIX, INTOUCH, etc KepwareOPC、ENETS7 OPC |
Diagnostic and parameter settings tool |
IE browser, default 192.168.1.188, BCDevice |
power supply mode Voltage type |
PLC port to power / external 24V 24VDC/100mA |
working temperature |
0~60℃ |
Working humidity |
95% Non-coagulation |
electromagnetic compatibility |
2014/30/EU |
attestation |
CE attestation |
Dimensions (L * W * H) |
115*27*75mm |
weight |
150g |