technical feature:
1. Built on the 35mm rail, LAN1 is dual-port RJ 45 with switch function, this port connects to PLC; LAN2 is single port RJ 45 and can be connected to touch screen or upper computer system; XCNet external 24VDC power supply.
2. Integrate WEB server to set device parameters and run diagnosis through the webpage; can be configured through BCDevice tool; can be configured from LAN1 or LAN2 port.
3. Implement the NAT function to map the IP address and port number of the PLC connected to the LAN1 port to any IP and port number of the LAN2 port.
4. The SmartIE series touch screen can be connected to S7-1200, S7-1500 and other PLC.
5. LAN2 port can support the ModbusTCP server function, and can map the PLC connected by LAN1 port to the ModbusTCP server of LAN2 port.
6. LAN2 port can support the ENETS7 protocol server function, which can map the PLC connected by LAN1 port into the ENETS7 protocol server of LAN2 port to facilitate the use of ENETS7 function.
7, support the server / client of up to 32 LAN2 / LAN1 concurrent model, LAN2 ports can support up to 32 host access.
8. Using ENETS7 protocol or ModbusTCP, it can realize high-level language programming (such as VB, VC, C #, etc.), realize data communication with PLC, and facilitate the development of production management system.
9. SCADA (OPC software) communicates with PLC in OPC mode.
10. Support the user side to achieve firmware update through Ethernet, provide free integrated more functional firmware, one hardware purchase, permanent upgrade.
Typical applications:
technical parameter:
product model |
XCNet-PN |
description |
Siemens series PLC Ethernet communication processor |
pigment |
Metal black |
situation display |
Pwr,LAN1,LAN2 |
Ethernet interface interface type transmission speed Protocol support TCP linker number |
IEEE 802.3 compatible, Link / Active indicator light, line order adaptive, support Auto-MDIX RJ 45 female socket 10/100Mbps S 7 TCP, ModbusTCP, ENETS7, et al 32 |
LAN1 interface (connected to PLC) interface type transmission speed Protocol support |
Ethernet RJ45*2 10/100M TCP/IP、S7TCP |
LAN2 interface (connect upper) interface type transmission speed Protocol support |
Ethernet RJ45*1 10/100M TCP/IP、S7TCP、ModbusTCP、ENETS7 |
programming software configuration software |
Protal V14 WINCC, configuration king, power control, Jay control, etc |
OPC software |
KepWare OPC |
Diagnostic and parameter settings |
IE Browser, default 192.168.2.188 (LAN1), default 192.168.1.188 (LAN2) BCDevice The Search Configuration Tool |
power supply mode Voltage type |
External to 24VDC 24VDC/100mA |
working temperature |
0~60℃ |
Working humidity |
90% Non-condensation |
way to install |
35mm guide rail installation |
electromagnetic compatibility |
2014/30/EU |
RoSH produce |
yes |
Anti-vibration |
4.5mm/30Hz/10Min |
ESD |
6KV |
Factory aging |
The 60 degree aging box operated for 168 hours and was power off 500 million times |
Communication stability |
Continuous 30 days of uninterrupted communication with PLC, 130 million communication 0 error |
attestation |
CE attestation |
Dimensions (L * W * H) |
90*24*65mm |
weight |
120g |